You are here
> Product Range >>
Scanning & Logging >>
Data Loggers |
| |
| |
|
Lectrotek’s range
of Temperature and Process Scanners, Data
Loggers and Data Acquisition Systems are used
for monitoring of critical equipment for their
healthy condition, safety, interlocking and
provide alarm & trip relays in case of fault
conditions such as exceeding/falling below set
values, or open sensor conditions etc. |
|
| |
|
|
|
 |
Application: Lectrotek
Scanners are used for monitoring equipment such as
HT motors, alternators, diesel engines, turbines,
boilers, HVAC systems etc. |
|
 |
Versions: solid-state (Model 881) and
microprocessor-based (Uniscan-series) |
|
 |
Universal inputs: programmable inputs for every
channels – RTDs, thermocouples, 4-20mA DC etc. |
|
|
|
 |
Features: choice of alarm/trip output relays,
Modbus communication, retransmission of maximum
value |
|
 |
Packaging in enclosures suitable for various
panel cutouts, rack-mount versions, field and
flameproof versions etc. |
|
 |
Comparative features are provided, along with
downloadable data sheets. |
| |
 |
|
DATA LOGGERS |
 |
| |
| |
|
|
|
|
|
|
|
|
Model |
|
|
|
 |
FEATURES |
 |
Site
programmable mixed inputs, ranges,
decimals, alarm/trip values. |
 |
8 (upto
32 if required) relays with C/O
contacts freely allocatable/grouped
to any channel alarm/trip. |
 |
All
functions –operation, configuration,
calibration and configuration from
keyboard. |
 |
Programmable inputs 4-20 mA
(Linear/Square Root), RTD, J,K,R,S,T
thermocouples |
 |
RS-232
Serial Communication port or RS485
port OPTIONAL. |
 |
16
inputs and 8 relay outputs standard
(refer factory for more
inputs/outputs) |
 |
2 nos
4-digit 7-segment LEDs for process
values, channel numbers, alarms etc. |
|
|
|
|
|
 |
SPECIFICATIONS |
 |
Description |
: |
µP-based 16/32 point
Temp./Process Scanner |
 |
Dimension |
: |
96 x 96 x 110 mm |
 |
Panel
cutout |
: |
92 x 92 mm |
 |
Capacity/Inputs |
: |
16/32
Channels |
 |
LED matrix
(status) |
: |
Not available |
 |
Inputs |
: |
Pt-100
RTD(Cu-53, Pt-46 etc. RTDs on
request).
Thermocouples ANSI Type
J,K,R,S,T(others on request).
4-20 mA, 0-5V DC |
 |
Power
Supply |
: |
90-270
VAC, 50 Hz. , 24VDC |
 |
Ranges |
: |
Programmable |
 |
Display(PV/channel no.) |
: |
4-digits (2nos.) |
 |
Alarm/trip
function |
: |
2
setpoints Hi/Low programmable for
every channels |
 |
Groups
for alarm/trip |
: |
Any
relay can be assigned to one or more
channels to form one or more groups |
 |
Relays |
: |
None, 2
/ 4 / 8 relays |
 |
Calibration/configuration |
: |
Via
membrane keyboard, enable input &
setpoint programming, calibration,
relay grouping functions |
 |
Communication Port |
: |
Rs-485
port with Modbus-RTU protocol |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model |
|
|
|
|
 |
FEATURES |
 |
Site
programmable mixed inputs, ranges,
decimals, alarm/trip values. |
 |
8 (upto
32 if required) relays with C/O
contacts freely allocatable/grouped
to any channel alarm/trip. |
 |
All
functions–operation, configuration,
calibration and configuration from
keyboard. |
 |
Programmable inputs 4-20 mA
(Linear/Square Root), RTD, J,K,R,S,T
thermocouples. |
 |
RS-232
Serial Communication port or RS485
port OPTIONAL. |
 |
16
inputs and 8 relay outputs standard
(refer factory for more
inputs/outputs) |
 |
2 nos
4-digit 7-segment LEDs for process
values, channel numbers, alarms etc. |
|
|
 |
SPECIFICATIONS |
 |
Description |
: |
µP-based 16/32 point
Temp./Process Scanner |
 |
Dimension |
: |
192 x 96 x 125 mm |
 |
Panel
cutout |
: |
186 x 92
mm |
 |
Capacity/Inputs |
: |
16/32/48/64 Channels |
 |
LED matrix
(status) |
: |
LEDs (Alarm/trip/open) |
 |
Inputs |
: |
Pt-100
RTD(Cu-53, Pt-46 etc. RTDs on
request).
Thermocouples ANSI Type
J,K,R,S,T(others on request).
4-20 mA, 0-5V DC |
 |
Power
Supply |
: |
90-270
VAC, 50 Hz. , 24VDC |
 |
Ranges |
: |
Programmable |
 |
Display(PV/channel no.) |
: |
4-digits (2nos.) |
 |
Alarm/trip
function |
: |
2
setpoints Hi/Low programmable for
every channels. |
 |
Groups for alarm/trip |
: |
Any
relay can be assigned to one or more
channels to form one or more groups. |
 |
Relays |
: |
None, 2
/ 4 / 8 relays |
 |
Calibration/configuration |
: |
Via
membrane keyboard, enable input &
setpoint programming, calibration,
relay grouping functions |
 |
Communication Port |
: |
Rs-485
port with Modbus-RTU protocol |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| |
|
|
|
|
|
Model |
|
|
|
 |
 |
FEATURES |
 |
Site
programmable mixed inputs, ranges,
decimals, alarm/trip values. |
 |
8 (upto
32 if required) relays with C/O
contacts freely allocatable/grouped
to any channel alarm/trip. |
 |
All
functions–operation, configuration,
calibration and configuration from
keyboard. |
 |
Programmable inputs 4-20 mA
(Linear/Square Root), RTD, J,K,R,S,T
thermocouples. |
 |
RS-232 Serial Communication port or
RS485 port OPTIONAL. |
 |
16
inputs and 8 relay outputs standard
(refer factory for more
inputs/outputs) |
 |
2 nos
4-digit 7-segment LEDs for process
values, channel numbers, alarms etc. |
|
|
 |
SPECIFICATIONS |
 |
Description |
: |
µP-based 16-64
point Temp./Process Scanner |
 |
Dimension |
: |
96 x 192 x 125 mm |
 |
Panel
cutout |
: |
92 x 186
mm |
 |
Capacity/Inputs |
: |
16/32/48/64 Channels |
 |
LED matrix
(status) |
: |
LEDs (Alarm/trip/open) |
 |
Inputs |
: |
Pt-100
RTD(Cu-53, Pt-46 etc. RTDs on
request).
Thermocouples ANSI Type
J,K,R,S,T(others on request).
4-20 mA, 0-5V DC |
 |
Power
Supply |
: |
90-270
VAC, 50 Hz. , 24VDC |
 |
Ranges |
: |
Programmable |
 |
Display(PV/channel no.) |
: |
4-digits (2nos.) |
 |
Alarm/trip
function |
: |
2
setpoints Hi/Low programmable for
every channels. |
 |
Groups for alarm/trip |
: |
Any
relay can be assigned to one or more
channels to form one or more groups. |
 |
Relays |
: |
None, 2
/ 4 / 8 relays |
 |
Calibration/configuration |
: |
Via
membrane keyboard, enable input &
setpoint programming, calibration,
relay grouping functions. |
 |
Communication Port |
: |
Rs-485
port with Modbus-RTU protocol |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| |
|
|
|
|
|
| |
Model |
|
|
|
|
 |
FEATURES |
 |
Site
programmable mixed inputs, ranges,
decimals, alarm/trip values. |
 |
8 (upto
32 if required) relays with C/O
contacts freely allocatable/grouped
to any channel alarm/trip. |
 |
All
functions–operation, configuration,
calibration and configuration from
keyboard. |
 |
Programmable inputs 4-20 mA
(Linear/Square Root), RTD, J,K,R,S,T
thermocouples. |
 |
RS-232 Serial Communication port or
RS485 port OPTIONAL. |
 |
16
inputs and 8 relay outputs standard
(refer factory for more
inputs/outputs) |
 |
2 nos
4-digit 7-segment LEDs for process
values, channel numbers, alarms etc. |
|
|
 |
SPECIFICATIONS |
 |
Description |
: |
µP-based 16/32
Temp./Process Scanner |
 |
Dimension |
: |
144x144 x 125 mm |
 |
Panel cutout |
: |
138 x 138 mm |
 |
Capacity/Inputs |
: |
16/32 Channels |
 |
LED matrix (status) |
: |
LEDs (Alarm/trip/open) |
 |
Inputs |
: |
Pt-100 RTD(Cu-53, Pt-46
etc. RTDs on request).
Thermocouples ANSI Type
J,K,R,S,T(others on
request).
4-20 mA, 0-5V DC |
 |
Power Supply |
: |
90-270 VAC, 50 Hz. ,
24VDC |
 |
Ranges |
: |
Programmable |
 |
Display(PV/channel no.) |
: |
4-digits (2nos.) |
 |
Alarm/trip function |
: |
2 setpoints Hi/Low
programmable for every
channels. |
 |
Groups
for alarm/trip |
: |
Any relay can be
assigned to one or more
channels to form one or
more groups. |
 |
Relays |
: |
None, 2 / 4 / 8 relays |
 |
Calibration/configuration |
: |
Via membrane keyboard,
enable input & setpoint
programming,
calibration, relay
grouping functions. |
 |
Communication Port |
: |
Rs-485 port with
Modbus-RTU protocol. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| |
|
|
|